Simodrive 611 Error 607 -
Follow this sequence to isolate the fault efficiently.
SimoCom U (free from Siemens, requires RS232 cable to X471 port) will read detailed internal logs. Look for:
Q: Can I clear Error 607 by cycling power?
A: Yes, but the error will return immediately unless the physical overvoltage condition is resolved. Cycling power resets the latch, not the cause.
Q: Does Error 607 damage the drive instantly?
A: Not instantly, but repeated overvoltage events stress the DC link capacitors and IGBTs. Continued operation with a faulty braking system will lead to catastrophic module failure. simodrive 611 error 607
Q: Can I use a generic braking resistor from another brand?
A: Yes, if resistance matches and wattage is equal or higher. However, ensure the mounting and thermal dissipation are adequate. Undersized resistors will fail within hours.
Q: Why does my 611 drive show 607 even though the mains voltage is stable?
A: Most likely internal drive aging (capacitors) or a chopper transistor that intermittently fails to turn off, dumping excess voltage into the DC link.
Based on the diagnostic findings, apply the appropriate solution: Follow this sequence to isolate the fault efficiently
| Finding | Action Item | | :--- | :--- | | Burned Contactor Coil | Replace the mains contactor. Verify coil voltage (typically 24VDC). | | Oxidized Aux Contact | Clean the auxiliary contact or replace the contactor. | | Loose Wiring | Re-terminate wires. Check crimps on ferrules. | | Missing Bridge/Jumper | Install the required jumper wire on the PSM terminals to simulate a closed contactor. | | Defective PSM Relay | Replace the Power Supply Module. Internal component repair is not recommended in the field due to SMD components. |
A common scenario: A vertical milling machine with a heavy spindle head. When the operator executes a rapid downward move and then an emergency stop, the spindle head tries to decelerate. The kinetic energy of the heavy axis, combined with gravity (which pulls downward even during deceleration), overwhelms the braking resistor. Error 607 appears.
Solution: The braking resistor was undersized for the duty cycle. Upgrading to a higher-wattage resistor with a more robust thermal mass—and adding an external fan—solved the issue permanently. Based on the diagnostic findings, apply the appropriate
This document details the diagnostic and repair procedures for Error 607 on the Siemens Simodrive 611 drive system. Error 607 is a critical startup fault indicating a failure in the power supply module's ability to engage or detect the status of the main power contactor (mains contactor). This error prevents the drive from enabling the DC Link voltage, rendering the machine inoperable.
If you have multiple identical axes, swap the power module of the faulty axis with a known good axis. Observe if the error moves with the module.